A NEURO-FUZZY TECHNIQUE FOR DISCRIMINATION BETWEEN INTERNAL FAULTS AND MAGNETIZING INRUSH CURRENTS IN TRANSFORMERS

نویسندگان

1 DEPARTMENT OF POWER ENGINEERING, UNIVERSITY OF BIRJAND, IRAN

2 DEPARTMENT OF POWER ENGINEERING, UNIVERSITY OF BIRJAND, IRAN

doi
10.22111/ijfs.2005.482
چکیده

This paper presents the application of the fuzzy-neuro method toinvestigate transformer inrush current. Recently, the frequency environment ofpower systems has been made more complicated and the magnitude of the secondharmonic in inrush current has been decreased because of the improvement of caststeel. Therefore, traditional approaches will likely mal-operate in the case ofmagnetizing inrush with low second component and internal faults with highsecond harmonic. The proposed scheme enhances the inrush detection sensitivity ofconventional techniques by using a fuzzy-neuro approach. Details of the designprocedure and the results of performance studies with the proposed detector aregiven in the paper. The results of performance studies show that the proposedalgorithm is fast and accurate.